Presentation Name | Type | Description |
Active Max Flow Setpoint |
Numeric |
The maximum flow setpoint presently in use by the UCM.Units: percent |
Active Min Flow Setpoint |
Numeric |
The minimum flow setpoint presently in use by the UCM.Units: percent |
Air Valve Drive Max: Local Ovrd |
Binary |
Indicates if at least one of the UCM’s thumbwheel inputs has been used to request that the air valve be driven to its maximum position/flow. 0=No, 1=Yes |
Air Valve Flow |
Numeric |
This is the calculated value of the flow in terms of cubic feet per minute (CFM). |
Air Valve Max Flow Stpnt: Local |
Numeric |
This property indicates the UCM-resident value of the maximum flow setpoint. This value is represented in terms of percent of the nominal size rating of the unit. |
Air Valve Min Flow Stpnt: Local |
Numeric |
This property indicates the UCM-resident edited cooling minimum flow setpoint. This value is represented in terms of percent of the nominal size rating of the unit. |
Air Valve Override Status |
Multi-State |
The flow override condition of the UCM. |
Air Valve Position |
Numeric |
Indicates the percent open position of the air valve. Range: 0 to 100% |
Air Valve Position Control Used |
Binary |
Indicates if the UCM is using position control. 0=No (Flow control) 1=Yes (Position control) |
Air Valve Size Index |
Numeric |
The index value used to determine the nominal CFM rating of the unit. |
Air Vlv Min Heat Flow Stpnt: Loc |
Numeric |
This property indicates the UCM-resident edited heating minimum flow setpoint. This value is represented in terms of percent of the nominal size rating of the unit. |
Auxiliary Temperature |
Numeric |
Indicates the temperature reported by the optional thermistor connected to the auxiliary sensor input on the UCM. Range: 25 to 190°F |
Calibration in Effect |
Binary |
Indicates if the UCM is presently calibrating its air valve (taking a zero flow reading). 0=Normal, 1=Recalibrate |
Call Status |
Multi-State |
This is the heat/cool call status of the UCM.0=" ": The UCM has a vote but is not currently calling for heating or cooling. |
Communication State |
Binary |
This property will be Down if the UCM is not communicating with the Central Control Panel or if the Central Control Panel is not communicating with the BCU. 0=Down, 1=Up |
Control Action |
Binary |
The heat/cool control action is automatically determined by the VariTrac II Central Control Panel for each UCM. The Central Control Panel determines a UCM’s heat/cool control action by comparing the system’s supply air temperature with the UCM’s zone temperature. The control action will indicate if there is warm or cold air in the supply duct. 0=Heating, 1=Cooling |
Control Mode |
Binary |
Indicates if the UCM is occupied. 0=Occupy, 1=Unoccupy |
Control Offset Value |
Numeric |
The value used by the control offset function to adjust the setpoints when the control offset is active.Range: 0 to 5F |
Cooling Setpoint Low Limit |
Numeric |
The active cooling setpoint does not go below this limit regardless of the source of the setpoint. Range: 45 to 100F |
Cooling Setpoint: Active |
Numeric |
The actual cooling setpoint in use by the UCM. Range: 45 to 95F |
Diag: Aux Sensor Fail |
Binary |
Indicates if the auxiliary temperature sensor has failed or does not exist. 0=Normal, 1=Failed |
Diag: Flow Sensor Fail |
Binary |
Indicates if the flow sensor has failed or does not exist.0=Normal, 1=Failed |
Diag: Low Battery Exists |
Binary |
Indicates if any of the wireless zone sensors associated with the UCM are reporting a low battery voltage. 0=No, 1=Yes |
Diag: Setpoint Fail Global |
Binary |
Indicates if all thumbwheel setpoints associated with this UCM have failed. This takes into account wireless thermostats, if used. 0=Normal, 1=Failed |
Diag: Zone Sensor Fail Global |
Binary |
Indicates if all the zone sensors associated with this UCM have failed. This takes into account wireless thermostats, if used. 0=Normal, 1=Failed |
Fan Control Method: Local |
Binary |
Indicates whether the UCM controls the parallel fan based on a temperature or flow setpoint. 0=Temp, 1=Flow |
Fan Control Offset |
Numeric |
If "Fan Control Method: Local" is "Temp", this offset determines when the parallel fan is energized. This property is specified as a temperature offset above the zone heating setpoint. Range: 0 to 10°F |
Fan Control Setpoint: Local |
Numeric |
If "Fan Control Method: Local" is "Flow", this setpoint determines when the parallel fan is energized. This setpoint is expressed as a percentage of the unit’s nominal size rating. Range: 0 to 100% |
Fan Exists |
Binary |
Indicates if the UCM is configured to control a fan.0=No Fan, 1=Fan Present |
Fan Output |
Binary |
The state of the UCM’s fan output. 0=Off, 1=On |
Fan Type |
Binary |
If the unit is configured to have a fan, this property indicates the fan type. 0=Parallel Fan, 1=Serial Fan |
Heat Active |
Binary |
The state of the UCM’s heat output(s). 0=Off, 1=On |
Heat Exists |
Binary |
Indicates if the UCM is configured to control its heat outputs. 0=No Heat Available, 1=Heating Available |
Heat Setpoint High Limit |
Numeric |
The active heating setpoint does not go above this limit regardless of the source of the setpoint. Range: 45 to 100F |
Heat Setpoint Offset: Local |
Numeric |
This value is subtracted from the thumbwheel setpoint to determine the active heating setpoint when the thumbwheel setpoint is enabled. Range: 2 to 10°F |
Heat/Cool Vote Enable |
Binary |
Indicates if the UCM is allowed to have a heat/cool vote and can influence the CCP’s changeover calculations.0=Disabled, 1=Auto |
Heating Setpoint: Active |
Numeric |
The heating setpoint currently being used by the UCM.Range: 45 to 95F |
Local Name |
Character |
This is the name of the UCM. This name differs from the "Object Name" in that it is stored at the VariTrac II Central Control Panel. |
Object Identifier |
Object ID |
Unique hexadecimal identifier of this particular object. This ID is used internally to identify a standard object. |
Object Name |
Character |
This property allows the assignment of a unique printable name to the object for user identification. |
Object Type |
Object Type |
This property designates the object’s type (e.g., VariTrac II CCP VAV UCM). |
Occupied Cool Setpoint: Local |
Numeric |
The UCM-resident edited occupied cooling setpoint.Range: 45 to 95°F |
Occupied Heat Setpoint: Local |
Numeric |
The UCM-resident edited occupied heating setpoint.Range: 45 to 95°F |
Occupied OA Required Setpoint |
Numeric |
Used to calculate the ventilation ratio during occupied operation. Units: CFM. Range: 0 to 100% of the unit’s nominal size rating. |
Parent ID |
Object ID |
Specifies the VariTrac II CCP System object to which this UCM belongs. |
Security Class |
Numeric |
This property identifies the security class to be used for access privileges to the given object. |
Software Revision |
Numeric |
The version of software loaded into the UCM. |
Thumbwheel Composite |
Numeric |
The composite thumbwheel setpoint which takes into account wireless thermostat values. Range: 45 to 95F |
Thumbwheel Setpoint Enable |
Binary |
Indicates if the thumbwheel setpoint is in use. 0=No Thermostat Setpoint,1=Thermostat Setpoint |
UCM Number |
Numeric |
The number (1-16) by which the UCM is known within the CCP. |
Unit Type |
Binary |
Indicates if the UCM is configured to control a VariTrane or VariTrac box. 0=Not VariTrac, 1=VariTrac |
Unit Type is Trane |
Binary |
Indicates if the UCM is configured to control a Trane unit (as opposed to a generic unit). 0=No, 1=Yes |
Unoccupied Cool Setpoint: Local |
Numeric |
The UCM-resident, edited, unoccupied cooling setpoint.Range: 45 to 95°F |
Unoccupied Heat Setpoint: Local |
Numeric |
The UCM-resident edited unoccupied heating setpoint. Range: 45 to 95°F |
Unoccupied Override: Local |
Binary |
Indicates if the local thumbwheel override to unoccupied is initiated. 0=No, 1=Yes |
Update Tag |
Numeric |
Object instance update tag. This tag is used to indicate that the nonvolatile memory resident data within the particular instance has changed. The workstation is the primary user of this property. |
Ventilation Ratio Calc |
Numeric |
This ratio is calculated by dividing the outdoor air requirement by the current flow or damper position. |
Zone Temp Composite |
Numeric |
The actual zone temperature being used by the UCM which takes into account wireless thermostat values, if used. Range: 0 to 125F |